What is the temperature in the machine room?
temperature is +72.5000F
, humidity is 38%
If it is too hot, over 82 degrees F,
- Check room 011 to see if it is really hot, or if there is
just a mistake with this sensor system.
- call Wayne, Tim, or Sandy
- turn on the other ac units by pushing the button on the control panel
- Call for air conditioning help. On weekends and evenings call
6-2344 (the heating plant). If you can't get through call safety
and security 6-2234 and have them page the troubleshooters.
- open the back door, and the door going outside three flights up.
- turn off the power to each computer in the clusters. If the clusters
are running there is no way that the temperature will drop on its own.